Methodology for analyzing environmental quality indicators in a dynamic operating room environment - 18/04/17
, Troy A. Markel, MD b, Howard W. Jones, MD c, Jennifer Wagner, PhD d, Damon Greeley, PE e, James H. Clarke, PhD a, Mark Abkowitz, PhD a, John Ostojic, IH fHighlights |
• | This study tests air quality indicators in a dynamic operating room environment. |
• | A mock surgical procedure led by a board-certified surgeon was used to simulate actual conditions in an operating room to provide realistic data. |
• | Levels of airborne contaminants in a health care setting can be accurately quantified using this testing protocol. |
• | Environmental quality indicators, such as number of particles, microbial contaminant load, air velocity, and temperature, provide insight to the effectiveness of heating, ventilation, and air conditioning systems. |
Abstract |
Background |
Sufficient quantities of quality air and controlled, unidirectional flow are important elements in providing a safe building environment for operating rooms.
Methods |
To make dynamic assessments of an operating room environment, a validated method of testing the multiple factors influencing the air quality in health care settings needed to be constructed. These include the following: temperature, humidity, particle load, number of microbial contaminants, pressurization, air velocity, and air distribution. The team developed the name environmental quality indicators (EQIs) to describe the overall air quality based on the actual measurements of these properties taken during the mock surgical procedures. These indicators were measured at 3 different hospitals during mock surgical procedures to simulate actual operating room conditions. EQIs included microbial assessments at the operating table and the back instrument table and real-time analysis of particle counts at 9 different defined locations in the operating suites. Air velocities were measured at the face of the supply diffusers, at the sterile field, at the back table, and at a return grille.
Results |
The testing protocol provided consistent and comparable measurements of air quality indicators between institutions. At 20 air changes per hour (ACH), and an average temperature of 66.3°F, the median of the microbial contaminants for the 3 operating room sites ranged from 3-22 colony forming units (CFU)/m3 at the sterile field and 5-27 CFU/m3 at the back table. At 20 ACH, the median levels of the 0.5-µm particles at the 3 sites were 85,079, 85,325, and 912,232 in particles per cubic meter, with a predictable increase in particle load in the non–high-efficiency particulate air-filtered operating room site. Using a comparison with cleanroom standards, the microbial and particle counts in all 3 operating rooms were equivalent to International Organization for Standardization classifications 7 and 8 during the mock surgical procedures.
Conclusions |
The EQI protocol was measurable and repeatable and therefore can be safely used to evaluate air quality within the health care environment to provide guidance for operational practices and regulatory requirements.
Le texte complet de cet article est disponible en PDF.Key Words : Air quality in operating rooms, Operating room ventilation rates, Air changes per hour, Surgical site infections, Mock surgical procedures, Environmental quality indicator (EQI)
Plan
| Funding/support: Funding and services were provided by the American Society of Healthcare Engineering and HCA FacilitiGroup Infrastructure Solutions. |
|
| Conflicts of interest: None to report. |
Vol 45 - N° 4
P. 354-359 - avril 2017 Retour au numéroBienvenue sur EM-consulte, la référence des professionnels de santé.
L’accès au texte intégral de cet article nécessite un abonnement.
Déjà abonné à cette revue ?